IN Brief:
- Vertiv expanded its 800V DC portfolio with compute pod and data hall conversion systems on 17 November.
- The range includes a 90kW 800V-to-54V shelf, 1.5MW pod power centre and 5MW solid-state transformer.
- Efficiency and transient-power figures are manufacturer ratings; customer pilots and technical validation are ongoing.
Vertiv has extended its 800V direct-current power portfolio from individual AI racks to compute pods and whole data halls. The equipment announced on 17 November adds centralised conversion options to the PowerDirect 5000 rack system introduced in May 2026. Vertiv now offers three locations for the main AC-to-800V DC conversion stage: beside the rack, ahead of a group of racks, or at the facility’s medium-voltage connection. Each approach places different demands on electrical distribution, protection and backup power.
The distinction is more than physical placement. High-density computing racks need a low-voltage supply at their processing boards, while the electricity available within a facility arrives through higher-voltage AC infrastructure. Supplying the racks through an intermediate DC distribution stage changes where conversion losses, backup equipment, conductors and protection devices must be accommodated. Vertiv has designed the new components to work with its DC busway and storage products, rather than treating an 800V supply as an isolated power module.
The existing PowerDirect 5000 Power Rack converts a 480V AC input to an 800V DC output, or to a split ±400V configuration. Vertiv states that it supports up to 800kW, using an assembly that accommodates 30 hot-pluggable 30kW power supply units and an integrated battery backup unit. The manufacturer describes at least 50 seconds of hold-up for the specified backup arrangement. That is a product-level claim, not a guaranteed duration for every combination of rack load, battery condition and installation.
Inside the computing enclosure, the PowerDirect 3000 uses a 1U, 19-inch shelf to reduce the 800V DC supply to 54V DC for compute trays. Its continuous nominal rating is 90kW, with up to 98.5% peak conversion efficiency reported by Vertiv. The company also specifies a short pulse capability of 180% for 0.5 milliseconds. Such a transient specification addresses rapid changes in processor loading; it cannot be used as the sustained power rating of the shelf or as an independently measured efficiency result for a complete rack.
At the next scale, the PowerDirect 9000 Power Center converts 480V AC to 800V DC for a row or compute pod with a stated capacity of 1.5MW. A PowerBar Track DC busway and protected tap-off points distribute that output to the rack converters. The power centre is described as scaling in 60kW increments using 27 hot-pluggable power supply units. Concentrating the conversion ahead of the row removes the requirement for a separate AC-to-800V rack system beside every compute enclosure, although the individual 800V-to-54V converters remain necessary.
Vertiv also identifies the EnergyCore Li5 800V battery cabinet as part of the pod arrangement. It is designed to connect directly to the DC bus and supply 200kW of continuous backup power at up to 98% conversion efficiency. Up to six cabinets can operate in parallel using active current sharing. This allows backup to be coordinated at the distribution level, but the actual ride-through duration will depend on battery configuration and connected demand; a 200kW power rating is not a statement of stored energy capacity.
At data hall scale, the PowerNexus MV SST is a liquid-cooled, containerised, 5MW solid-state transformer that converts medium-voltage AC directly to 800V DC. Vertiv says the architecture can bypass two or three intermediate conversion stages and provide galvanic isolation, with rated AC-to-DC efficiency reaching 98%. Its bidirectional arrangement is designed for connection to energy storage, allowing the electrical system to manage changes in loading. The effect on grid power quality will depend on the installed control and protection arrangements as well as the transformer itself.
These architectures carry different installation implications. The rack-level arrangement is directed at retrofits and facilities with mixed AC and DC equipment, while pod conversion places more electrical equipment in a shared power centre. A medium-voltage solid-state transformer requires closer coordination with the building’s primary distribution, fault protection, earthing and servicing arrangements. Consolidating conversion may reduce the number of stages, but it also changes the size of the electrical loads affected by a common conversion or distribution fault.
Direct-current fault management cannot simply duplicate established AC procedures. Vertiv lists touch-proof busbars, high-voltage isolation, midpoint grounding, ground-fault detection and arc-flash prevention among the protection features in the portfolio. DC circuits require particular attention to interruption and isolation because current does not pass through a natural zero crossing in the same way as alternating current. Protection settings, equipment selection and maintenance access therefore remain part of the complete system design.
The expanded equipment is being exhibited at SC26 from 17 to 22 November. Vertiv reports customer pilots, technical validation and collaborative development, but its announcement does not establish a single commercial deployment timetable for every product or independently verified efficiency figures for installed systems. Rack retrofits, shared compute pods and medium-voltage data hall designs will require different approaches to integration, particularly when existing AC distribution and backup systems must remain in service.