Schneider expands European liquid cooling manufacturing

Schneider expands European liquid cooling manufacturing

Schneider Electric will double Italian production of coolant distribution units. The expansion includes higher-capacity chiller manufacturing and a new validation laboratory supporting thermal management equipment rated at up to 5MW.


IN Brief:

  • Coolant distribution unit manufacturing capacity at Conselve will double from January 2027.
  • Production capacity for large chillers is scheduled to increase by 50% before the end of 2026.
  • A laboratory scheduled for completion in December 2027 will triple existing thermal management equipment testing capacity.

Schneider Electric is expanding its European liquid cooling manufacturing operations at Conselve, Italy, doubling production capacity for coolant distribution units as increasing semiconductor power densities place additional demands on computing infrastructure.

The additional coolant distribution unit (CDU) capacity is scheduled to become available from January 2027, alongside a 50% increase in manufacturing capacity for large chillers before the end of 2026.

The investment follows Schneider Electric’s acquisition of a 75% controlling interest in thermal management specialist Motivair in 2025. It will also extend the company’s engineering and equipment validation infrastructure through a new laboratory scheduled for completion in December 2027.

The laboratory will triple existing testing capacity and accommodate chillers rated at up to 4MW, CDUs with capacities reaching 5MW, and computer room air handling and fan wall equipment rated at up to 800kW.

Higher power consumption within advanced computing systems has intensified the thermal constraints associated with individual semiconductor packages. Electrical losses generated within processors must be transferred through packaging materials and thermal interfaces before being removed by the associated cooling equipment.

The temperature difference across that cooling path depends on the heat being transferred and its effective thermal resistance. Increasing semiconductor power consumption without reducing thermal resistance therefore raises the temperature at which the device operates relative to its surrounding cooling medium.

Higher junction temperatures can increase semiconductor leakage currents and influence long-term component reliability, while exceeding specified operating limits can require reductions in processor performance.

Conventional air cooling transfers heat from electronic components into a moving air stream through heatsinks and other thermally conductive structures. Its performance depends on the available heat transfer surface area, air temperature, airflow characteristics, and the geometry of the electronic assembly.

As package and system power densities increase, supplying sufficient airflow through compact electronic equipment can become increasingly difficult. Higher airflow rates also increase fan energy consumption and pressure losses across heatsinks and equipment enclosures.

Direct-to-chip liquid cooling replaces part of that thermal pathway with a liquid circuit. Cold plates mounted against processors transfer heat into circulating coolant, allowing energy to be transported away from the electronic assembly without relying exclusively on airflow through the equipment.

A CDU manages the coolant circuit serving those electronic assemblies. In liquid-to-liquid configurations, heat exchangers transfer energy from the technology cooling circuit into a separate facility cooling circuit, allowing their operating pressures, fluid composition, and temperatures to be managed independently.

The cooling capacity required of a distribution unit depends on the aggregate thermal load connected to it and the temperature rise permitted within the coolant circuit. As an illustrative engineering calculation, transferring 5MW of thermal energy through water with a temperature rise of 10°C would require a mass flow rate of approximately 120kg per second.

Actual system flow requirements depend on the coolant composition, temperature conditions, operating limits, and configuration of the equipment.

Distributing that flow between numerous parallel electronic assemblies introduces hydraulic engineering challenges. Individual cold plates and connecting pipework can exhibit different flow resistance characteristics, potentially producing uneven coolant delivery despite sufficient aggregate capacity at the distribution unit.

Instrumentation and control electronics provide the measurements needed to identify those conditions. Temperature sensors, pressure transducers, and flow measurement devices can be integrated into the cooling system, with embedded controllers adjusting pump operation according to changing thermal loads and hydraulic conditions.

The reliability and response characteristics of those electronic subsystems influence the performance of the overall cooling architecture. Fault detection, measurement accuracy, and control stability become particularly important where multiple high-power electronic systems depend on shared coolant infrastructure.

Schneider Electric’s planned laboratory will provide facilities for validating higher-capacity cooling equipment under controlled operating conditions. Testing can establish how complete systems respond to changes in thermal load, coolant supply temperature, and hydraulic resistance before they are incorporated into operational installations.

The Conselve site already accommodates manufacturing, research and development, engineering, and training activities. Expanding its validation infrastructure alongside production capacity will allow Schneider Electric to assess larger cooling systems within the same industrial environment in which they are developed and manufactured.

The first manufacturing capacity increases are scheduled to take effect over the coming months, with the laboratory providing additional equipment validation capabilities from December 2027.


Stories for you


  • Agile Analog supplies ASPEED with silicon security IP

    Agile Analog supplies ASPEED with silicon security IP

    Agile Analog has supplied ASPEED with physical silicon security IP. Six analogue and mixed-signal blocks have been integrated into the AST1080 security processor, supporting physical anti-tamper protection alongside post-quantum cryptographic capabilities.


  • Schneider expands European liquid cooling manufacturing

    Schneider expands European liquid cooling manufacturing

    Schneider Electric will double Italian production of coolant distribution units. The expansion includes higher-capacity chiller manufacturing and a new validation laboratory supporting thermal management equipment rated at up to 5MW.