IN Brief:
- Four technology areas address electrical protection, conversion, distribution, and industrial motor control.
- Semiconductor switching enables current interruption on microsecond timescales, subject to circuit design and fault conditions.
- Hybrid AC/DC distribution requires coordinated sensing, gate driving, thermal management, and protection.
Schneider Electric has unveiled a portfolio of power electronics technologies incorporating semiconductor switching, digital control, and sensing into electrical distribution equipment, targeting industrial installations and infrastructure with increasingly complex power architectures.
Presented at the McLaren Technology Centre in Woking on 24 November, the portfolio includes the InterLink Converter for AC/DC system integration, solid-state circuit breakers for DC protection, software-defined low-voltage distribution, and TeSys iMCC for industrial motor control.
The technologies address the increasing presence of electronically controlled loads, energy storage systems, and distributed generation within electrical installations, extending semiconductor design considerations into equipment traditionally dominated by electromechanical switching and protection mechanisms.
Schneider Electric says its power electronics technologies can perform switching, conversion, and current interruption within microseconds while providing operating information and diagnostic capabilities.
Rapid interruption is particularly valuable within DC distribution systems, where fault currents cannot be interrupted using the natural periodic current zero crossings present in AC circuits. Conventional circuit breakers must physically separate electrical contacts and extinguish the resulting arc, whereas semiconductor switches control current through changes in their conductive state.
Current sensing circuits must recognise abnormal conditions, protection logic must distinguish faults from acceptable transient behaviour, and gate driving circuitry must reliably command the switching devices. The speed of the semiconductor itself represents only one element of the total fault response time.
Energy stored in circuit inductance must also be managed during current interruption. Without an appropriate path for this energy, the resulting voltage transient can exceed the semiconductor’s blocking capability, potentially damaging the protection device.
Solid-state circuit breaker design consequently requires coordination between semiconductor selection, sensing bandwidth, switching behaviour, and transient energy management. Parasitic inductance within the physical assembly can further influence voltage overshoot and device stress, making the layout of conductive paths an important consideration.
Thermal performance introduces another distinction between electronic and mechanical switching. Mechanical contacts generally exhibit low conduction losses when closed, whereas semiconductor devices dissipate energy continuously while carrying current. The resulting temperature rise depends on device characteristics, operating current, packaging, and the effectiveness of the thermal path between the semiconductor junction and its surroundings.
Hybrid protection architectures can combine mechanical and electronic elements to address different operating requirements. Semiconductor switches may provide rapid fault response, while mechanical components can establish physical isolation or carry current with lower continuous conduction losses.
Schneider Electric’s InterLink Converter addresses another aspect of hybrid distribution, providing an electronically controlled interface between AC and DC systems. Regulating the exchange of electrical energy between voltage domains creates opportunities to coordinate distributed energy resources and electronically controlled loads.
Converter design introduces constraints associated with switching losses, electromagnetic interference, magnetic component selection, and the stability of interacting control loops. Where multiple converters share a distribution network, their individual control responses can influence the behaviour of the wider system.
The TeSys iMCC technology extends the portfolio into industrial motor control, combining developments in switching, measurement, protection, and programmable control. Digitally implemented functions can provide more detailed operating information than conventional electromechanical systems, while their supporting electronics must remain dependable under challenging electrical and environmental conditions.
Electrical noise, supply disturbances, elevated temperatures, and long equipment lifecycles all influence hardware and firmware design. The separation of sensitive measurement circuitry from high-energy switching paths becomes particularly important as additional control functions are incorporated into compact electrical equipment.
Software-defined distribution introduces further opportunities to modify equipment behaviour through configuration rather than physical changes to wiring or protection hardware. Programmable settings must remain consistent with the electrical and thermal capabilities of the underlying switching devices throughout the equipment’s operating life.
Schneider Electric’s wider development of power electronics-based distribution architectures brings these individual functions together within a broader electrical system. As protection, conversion, and control become more closely integrated, qualification must address the combined behaviour of their supporting electronic subsystems under normal operating conditions, transient disturbances, and electrical faults.